Article source:
Application
These halogen-free, flame retardant cables are designed for frequency converter controlled AC drives, suitable for xed installation and occasional free exing indoors in dry, damp and wet conditions, as well as outdoors for low mechanical stress.
Standards
DIN VDE 0250
IEC 60092-353
Construction
Conductor: Stranded bare copper, class 5 according to DIN VDE 0295/IEC 60228.
Protective Conductor: Stranded bare copper, class 5 according to DIN VDE 0295/IEC 60228. For
cross sections > 16mm² the protective conductor is divided into 3 cores.
Insulation: Halogen free special XLPE according to IEC 60502-4.
Screen: Al coated tape + tinned copper wires braid.
Sheath: Halogen free compound HM4. Halogen free PUR can be offered upon request.
Technical Data
Rated Voltage Uo/U (Um) |
600/1000V |
Operating Temperatures |
-5℃~+90℃ |
Minimum Bending Radius |
flexing: 20×OD; fixed: 10×OD |
Flame Retardant |
IEC 60332-3 |
Halogen Free |
IEC 60754 |
Gases Corrosively |
IEC 60754 |
Ozone Resistant |
Yes |
UV Resistant |
Yes |
Dimensions and Weight
Construction |
Nominal Overall Diameter |
Nominal Weight |
No. of cores×mm² |
mm |
kg/km |
4×1.5 |
11.0 |
230 |
4×2.5 |
12.5 |
300 |
4×4 |
15.5 |
390 |
4×6 |
17.5 |
420 |
4×10 |
19.5 |
780 |
3×16+3×2.5 |
22.5 |
820 |
3×25+3×4 |
26.0 |
1150 |
3×35+3×6 |
29.5 |
1550 |
3×50+3×10 |
35.0 |
2400 |
3×70+3×10 |
38.5 |
3100 |
3×95+3×16 |
44.0 |
4200 |
3×120+3×16 |
48.0 |
4630 |
3×150+3×25 |
53.0 |
5880 |
3×185+3×35 |
58.0 |
7200 |
3×240+3×50 |
66.0 |
9600 |
3×300+3×50 |
73.0 |
11530 |